C-20 / Appendix C - Hardware Installation Guide

CI-ControlWave EFM

Downloading the Application Load


Any ControlWave EFM must have a configured application load before it can be placed into
operation. For units not shipped with the ‘Standard Load,’ this will require connection of the
ControlWave EFM to a PC running Windows NT (4.0 or higher), Windows 2000 or Windows
XP Professional and equipped with ControlWave Designer software & OpenBSI software.
Configuration of the application load must be performed by an individual familiar with the
various programming tools. The following software user documentation is referenced:

Getting Started with ControlWave Designer Manual - D5085
ControlWave Designer Reference Manual - D5088
Open BSI Utilities Manual - D5081
Web_BSI Manual - D5087

An application load download can be initiated, i.e., from ControlWave Designer, or from the
OpenBSI 1131 Downloader for ControlWave EFM Nodes.


1. Make sure that the System Controller Module’s Mode Switch (SW1) is set in ‘Local Mode,’

i.e., SW1-1 set to the OPEN (Right) position and SW1-2 set to the CLOSED (Left)
position.


Note: From the factory, COM1 defaults to 115.2 kbd (RS-232) using the Inter-

net Point to Point Protocol (PPP). Don’t connect COM1 to a PC unless
the PC’s RS-232 port in question has been configured for PPP.


2. Once the ControlWave EFM project has been defined, communications and con-

figuration parameters have been set, perform the download according to either
ControlWave Designer’ (see D5088 - chapter 11) or ‘The Open BSI 1131 Downloader’
(see D5081 - Chapter 7).

3. After the download has been completed leave the System Controller Module’s Mode

Switch (SW1) in the ‘Local Mode’ position.

LED Checks


All ControlWave EFM Modules contain light emitting diodes (LEDs) that provide
operational and diagnostic functions. ControlWave EFM LED designations and functions
are provided in Table C-6. A brief synopsis of the individual module LEDs is provided as
follows:

SCM:

1 IDLE LED, 1 Watchdog LED, & 6 System Status LEDs

CPUM: 2 LEDs per Comm. Port = 6
ECOM1: 2 LEDs per Comm. Port = 8
ECOM2: 2 LEDs per Comm. Port = 8
AI/OM: None
DI/O:

1 LED per DI x 12 = 12 DI LEDs, 1 LED per DO x 4 = 4 DO LEDs

HSC:

1 LED per HSC x 4 = 4 HSC LEDs

MI/OM: None