CI-ControlWave EFM

Table 4-2 - RS-232 Ports (COM1/2/4/8 and RS-485 Ports COM3//5/9

Connector Pin Assignments

Pin

#

Signal

RS-232

Description:

RS-232 Signals

Signal

RS-485

Description:

RS-485 Signals

1

DCD

Data Carrier Detect Input

N/A

2

RXD

Receive Data Input

RXD-

Receive Data - Input

3

TXD

Transmit Data Output

TXD-

Transmit Data - Output

4

DTR

Data Terminal Ready Output

TXD+

Transmit Data + Output

5

GND

Signal/Power Ground

ISOGND

Isolated Ground

6

DSR

Data Set Ready Input

RXD+

Receive Data + Input

7

RTS

Request To Send Output

N/A

8

CTS

Clear To Send Input

N/A

9

N/A

N/A

Figure 4-1 - DB9 9-Pin Connector

Associated with COM1, COM2, COM3, COM4, COM5, COM8 & COM9

4.3 SYSTEM CONTROLLER MODULE

4.3.1 Input Power Specs.

Note: Voltages are dc unless otherwise specified.


Operating Range:

+4.5/4.9V to +16.0V (+6V Input Supply) (Shutdown occurs
at +4.72/4.33V nominal)

+9.6/10.3V to +16.0V (+12V Input Supply) (Shutdown
occurs at +10.29/9.56V nominal)


Output Voltages:

+3.3Vdc

±1%


Output Current:

1A Max. @ 3.3Vdc

Output Ripple P/P:

+3.3V Output: 10mV

Input Current:

With Supply Loading of 3.3V @ 1.0A

Vin @ +6V - Iin Max. TBDA

Vin @ +12V - Iin Max. TBDA

Fusing:

1A Slow Blow 5x20mm Fuse


Electrical Isolation:

None


Surge Suppression:

16V Transorb to DGND and Chassis

Meets ANSI/IEEE C37.90-1978


Terminations:

Pluggable, maximum wire size is 16 gauge