F-30 / Appendix F

CI-ControlWave EFM

Figure F-18B - (1992 AGA3) Orifice Flow Equation Setup Web Page


Adjust Press. - Users enter Average Barometric Pressure here (psia).

Diff. Press. - Actual value in use is displayed here.

Static Pressure - Actual value in use is displayed here.

Temperature - Actual value in use is displayed here.

Spec. Gravity - Specific Gravity of the gas being measured is displayed here.

Z Flowing - Flowing compressibility Factor, Zf, generated from the AGA8 calculation
referenced to upstream conditions.

Z Base - Base compressibility Factor from the AGA8 Gross calculation.

Base Temperature - Required and Contract Base Temperate is entered here (Deg. F).

Base Pressure - Required or Contract Base Pressure is entered here (psia). The following
outputs from the AGA3 calculation are displayed:

MSCF/H - Flow rate in thousands of standard cubic feet per hour

Low Flow Cut Off - Cutoff (if the DP drops below the low flow cut off value) or OK

C Prime - Orifice Flow Constant

Fn - Numeric Conversion factor which includes Ev (the velocity of approach factor)

CD - Orifice Coefficient of Discharge