The power supply operates from +4.5/+4.9 to +16Vdc or +9.6/10.3 to +16Vdc with the
nominal input supply configuration (+6V or +12V) user configured via on-board jumpers. A
supervisory circuit monitors the incoming power and the supply voltages. The isolated
supplies are shut down when the incoming voltage drops below +4.5V for a +6V system or
+9.6V, for a +12V system.

An external battery monitor is composed of an Analog to Digital Converter (ADC) and
interface circuitry.

JP5, JP6, JP7, JP8 & JP9
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System

JP1 - Factory Configured

(Not Shown)

JP5 - Power Fail Trip Point Selection
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System

JP6 - Supply Shutdown Trip Point Selection
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System

JP7 - 1.2V Reference Source Current Selection
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System

JP8 - Supply Shutdown Trip Point Hysterisis
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System

JP9- Power Fail Trip Point Hysterisis
1-to-2 Installed = 12V Bulk System
2-to-3 Installed = 6V Bulk System

P1

1

1

2

JP9

JP8

JP6

JP5

JP7

1

1

1

CR27

CR26

CR25

CR24

(Red)

IDLE LED

(Red)

Sta us LEDs

TB1

Input Power

Connector

(Red)

WATCHDOG LED

TB2

RTD Interfa ce

Connector

P2

MVT Interfa ce

Connector

J2

Displa y Intf.

Connector

1A

J2

RJ-45

TB1-1
TB1-2
TB1-3

(+4.5/4.9Vdc to +16.0Vdc for +6V supply)

+VIN (+9.6/10.3Vdc to +16.0Vdc for +12V supply)

-VIN (Supply Ground)

Chassis Ground (CHASSIS)

SW1 = Mode Switch

Figure 1-6 - ControlWave EFM System Controller Module