2-14 / Installation & Operation

CI-ControlWave EFM

For safety reasons and to prevent accidental damage to a user supplied external bulk DC
Power Supply, it is recommended that pluggable Terminal Block connector TB1 be discon-
nected from the SCM until the entire unit has been wired, and hardware configured.
Sections 2.3.9.1 & 2.3.9.2 provide details on DC Power Connector TB1 wiring.

Table 2-1 - System Controller Module Switch SW1 – User Configurations

Switch

Function

Setting - (ON = Factory Default)

SW1-1/2 Recovery/Local

Mode

Both Open/Closed = Recovery Mode

SW1-1 Open (right) & SW1-2 Closed (left) = Local Mode

Note: Only SCM Switch SW1 settings listed in this table have been tested.

2.3.3 CPU Module & ECOM Module Configuration


To configure the CPU Module, Jumpers must be set (see Figure 2-9), DIP-Switches must be
set (see Section 2.3.3.1) and Communication Ports must be wired (see Sections 2.3.3.2
through 2.3.3.3). The CPU Module resides in Base Chassis Backplane Slot #2 (see Figure 2-
2). Backplane Slot #2 provides 44-pin female interface connector P2 on the bottom and 36-
pin female interface connector P3 on the top.

2.3.3.1 CPU Module Switch Configuration

ControlWave EFM CPU Module DIP-Switches must be set for the desired performance
options. Tables 2-2, 2-3 and 2-6 provide an overview of switch settings.

SW2-1 set OFF will disable the system from entering a watchdog state when a crash or
system hangup occurs. Setting SW2-1 OFF prevents the system from automatically
restarting.

SW2-2 set OFF prevents changing the Soft Switches, other configurations and FLASH files,
i.e., these items are locked. To change Soft Switch, configuration and FLASH files SW2-2
must be set to the ON position (see Section 2.4.4).

Table 2-2 - CPU Bd. Switch SW2 - User Configurations

Note: Except for SW2-4, ON = Factory Default

Switch

Function

Setting - (ON = Factory Default)

SW2-1 Watchdog

Enable ON = Watchdog circuit is enabled

OFF = Watchdog circuit is disabled

SW2-2

Lock/Unlock

Soft Switches

ON = Write to Soft Switches and FLASH files

OFF = Soft Switches, configurations and FLASH files are locked

SW2-3

Use/Ignore

Soft Switches

ON = Use Soft Switches (configured in FLASH)

OFF = Ignore Soft Switch Configuration and use factory defaults

SW2-4

Core Updump

See Section 3.6

ON = Core Updump Disabled

OFF = Core Updump Enabled via Mode Switch (SW1) on SCM

SW2-5 SRAM

Control

ON = Retain values in SRAM during restarts

OFF = Force system to reinitialize SRAM

SW2-6

System Firmware

Load Control *

ON = Enable remote download of System Firmware

OFF = Disable remote download of System Firmware

SW2-7 N/A

SW2-8 Enable

WINDIAG ON = Normal Operation (don’t allow WINDIAG to run test)

OFF = Disable boot project (allow WINDIAG to run test)

* = Boot PROM version 4.7 or higher and System PROM version 4.7 or higher