CI-ControlWave EFM

Table 2-4A - RS-232 Ports (1/2/4/8) and RS-485 Ports (3/5/9) Pin Assignments

Pin

#

Signal

RS-232

Description:

RS-232 Signals

Signal

RS-485

Description:

RS-485 Signals

1

DCD

Data Carrier Detect Input

N/A

2

RXD

Receive Data Input

RXD-

Receive Data - Input

3

TXD

Transmit Data Output

TXD-

Transmit Data - Output

4

DTR

Data Terminal Ready Output

TXD+

Transmit Data + Output

5 GND Signal/Power

Ground

GND/ISOGND* Ground/Isolated

Ground

6

DSR

Data Set Ready Input

RXD+

Receive Data + Input

7

RTS

Request To Send Output

N/A

8

CTS

Clear To Send Input

N/A

* ISOGND on Isolated RS-485 Ports Only! Note: Pin-9 not used

Table 2-4B - RS-232 Port (COM1) Connector Pin Assignments

(COM1 Connectors, i.e., Circular Local Port & D-Type ‘C1’ on CPU)

COM1

Pin #

Signal

RS-232

Description:

RS-232 Signals

Wire

Color

Local Port

RS-232 Pin #

1

DCD

Data Carrier Detect Input

Green

1

2

RXD

Receive Data Input

White

7

3

TXD

Transmit Data Output

Red

2

4

DTR

Data Terminal Ready Output

Brown

4

5 GND Power

Ground

Black

6

6

DSR

Data Set Ready Input

7*

RTS

Request To Send Output

8*

CTS

Clear To Send Input

*

=

RTS connected to CTS

Control

EFM

Wave

9-Pin Female

“D” Connector

(Looking into

Wire Terminal Side

of

Cable Connectors)

3 = TXD

6 = DSR

7 = RTS

8 = CTS

4 = DTR

2 = RXD

1 = DCD

5 = GND

To P2 Pin-4

To P2 Pin-2

To P2 Pin-7

To P2 Pin-3

To P2 Pin-6

To P2 Pin-5

To P2 Pin-1

9-Pin Female

“D” Connector

3 = TXD

6 = DSR

7 = RTS

8 = CTS
4 = DTR

2 = RXD

1 = DCD

5 = GND

or

vice

versa

Figure 2-13A - PC Connected to ControlWave EFM via D-Type Local Port