Emerson Process Management ControlWave EFM 3808 User Manual

Page 89

Advertising
background image

CI-ControlWave EFM

Installation & Operation / 2-37

Figure 2-23 - Non Isolated Mixed I/O Module Configuration Diagram


2.3.4.7.1 Mixed I/O Module Configurations


Mixed I/O Module Configuration Jumpers W1 through W28 must be set per Table 2-11.

Table 2-11 - Non Isolated Mixed I/O Module Jumper Assignments

Jumper

Purpose

Notes

W1*

Configures optional AO for

Voltage or Current Output

Pins 1-2 installed = AO set for Current Output

Pins 2-3 installed = AO set for Voltage Output

W2

Configures optional AO for

Voltage or Current Output

Pins 1-2 installed = AO set for Voltage Output

Pins 2-3 installed = AO set for Current Output

W5 & W6

HSC1 Current Control

Pins 1-2 installed = for additional 2mA load

Pins 2-3 installed = 200uA Source no 2mA load

W7 & W8

HSC2 Current Control

Pins 1-2 installed = for additional 2mA load

Pins 2-3 installed = 200uA Source no 2mA load

W9 & W10

Configures HSC1 and HSC2

Debounce (respectively)

Pins 1-2 installed = Enables HSC Debounce

Pins 2-3 installed = Disabled HSC Debounce

W11 - W16

Configures DI1 through DI6

Current (respectively)

Pins 1-2 installed = 2mA Source Current

Pins 2-3 installed = 60uA Source Current

W17 - W22

DI/O1 through DI/O6 Point

Selection (respectively)

Pins 1-2 installed = Digital Input Operation

Pins 2-3 installed = Digital Output Operation

Advertising