CI-ControlWave EFM

Table C-1 - CPU Bd. Switch SW1 - Force Recovery Mode/Battery Enable

Switch

Function

Setting - (OFF = Factory Default)

SW1-3 Force Recovery

Mode

ON = Force recovery mode (via CW Console)

OFF = Recovery mode disabled

Note: SCM Switch SW1 can also be used for Force Recovery Mode operation

Table C-2 - CPU Bd. Switch SW2 - User Configurations

Note: Except for SW2-4, ON = Factory Default

Switch

Function

Setting - (ON = Factory Default)

SW2-1 Watchdog

Enable ON = Watchdog circuit is enabled

OFF = Watchdog circuit is disabled

SW2-2

Lock/Unlock

Soft Switches

ON = Write to Soft Switches and FLASH files

OFF = Soft Switches, configurations and FLASH files are locked

SW2-3

Use/Ignore

Soft Switches

ON = Use Soft Switches (configured in FLASH)

OFF = Ignore Soft Switch Configuration and use factory defaults

SW2-4

Core Updump

See Section 3.6

ON = Core Updump Disabled

OFF = Core Updump via Mode Switch (SW1) on SCM

SW2-5 SRAM

Control ON = Retain values in SRAM during restarts

OFF = Force system to reinitialize SRAM

SW2-6

System Firmware

Load Control *

ON = Enable remote download of System Firmware

OFF = Disable remote download of System Firmware

SW2-8

Enable

WINDIAG

ON = Normal Operation (don’t allow WINDIAG to run test)

OFF = Disable boot project (allow WINDIAG to run test)

* = Boot PROM version 4.7 or higher and System PROM version 4.7 or higher

Table C-3 provides CPU Switch SW3 (COM3) and ECOM Switch SW1 COM5/9 RS-485
communication port settings.

Table C-3 - CPU Bd. Switch SW3 for COM3 & ECOM Bd. Switch SW1 for COM5/9

Loopback & Termination Control

Switch

#

RS-485 Function

Switch ON

Setting

1

TX+ to RX+ Loopback

ON - Only for Diagnostics

2

TX- to RX- Loopback

ON - Only for Diagnostics

3

100 Ohm RX+ Termination

ON - End Nodes Only

4

100 Ohm RX- Termination

ON - End Nodes Only

5

N/A

ON - Slew Rate Enabled

6

(see note

2)

Slow Slew Rate

ISO485 ONLY

ON - Slow Rate Enabled

OFF - Fast Rate Enabled

7

RX+ Bias (End Node)

ON - End Nodes Only

8

RX- Bias (End Node)

ON - End Nodes Only

Note 1: Closed = Switch set ON

Note 2: Switch SW3 (COM3) = N/A


Step 1. Hardware Configuration (Continued)

4. Configure/Connect appropriate communication port(s) (see Sections 2.3.3.2). Connect

COMM. Port 1 or 2 of the ControlWave EFM (depending on CPU Switch SW1 settings
- see Tables C-2 & C-3) to a Communication Port of a PC (typically PC COMM. Port 1).
Note: Also see Section 2.4.4.