Figure 35: Airflow Through the EX8208 Switch Chassis

If you are mounting the switch on a rack or cabinet along with other equipment, ensure
that the exhaust from other equipment does not blow into the intake vents of the
chassis.

Leave at least 24 in. (61 cm) both in front of and behind the switch. Allow at least 6 in.
(15.2 cm) of clearance on each side of the chassis. Leave adequate space at the front
of the switch for service personnel to remove and install hardware components. NEBS
GR-63 recommends that you allow at least 30 in. (76.2 cm) in front of the rack or
cabinet and 24 in. (61 cm) behind the rack or cabinet. See Figure 36 on page 103.