AC Power Cord Specifications for an EX8200 Switch

Each AC power supply has a single AC appliance inlet located on the power supply that
requires a dedicated AC power feed. Most sites distribute power through a main conduit
that leads to frame-mounted power distribution panels, one of which can be located at
the top of the rack that houses the switch. An AC power cord connects each power supply
to the power distribution panel.

Each detachable AC power cord is 2.5 meters (approximately 8 feet) long. The appliance
coupler at the female end of the cord inserts into the AC appliance inlet on the faceplate
of the AC power supply. The coupler type is C19 as described by the International
Electrotechnical Commission (IEC) standard 60320. The plug at the male end of the
power cord fits into the power source outlet that is standard for your geographical location.

NOTE: In North America, AC power cords must not exceed 4.5 meters (approximately
15 feet) in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA
75, 5-2.2) and 210-52 and Canadian Electrical Code (CEC) Section 4-010(3). The cords
shipped with the switch are in compliance.

Table 47 on page 112 lists the AC power cord specifications for an EX8200 switch for the
countries and regions listed in the table.

Table 47: AC Power Cord Specifications for an EX8200 Switch

Plug Standards

Electrical Specifications

Country/Region

AS/NZS 3112

250 VAC, 15 A, 50 Hz

Australia

GB 1002

250 VAC, 16 A, 50 Hz

China

CEE (7) VII

250 VAC, 16 A, 50 Hz

Europe (except Italy,
Switzerland, and United
Kingdom)

CEI 23-16

250 VAC, 16 A, 50 Hz

Italy

NEMA 6–20

NEMA L6–20

250 VAC, 16 A, 50 Hz

Japan