Required tools, Electrical specifications – Sun Microsystems Sun Fire V880 User Manual

Page 22

Advertising
background image

Installation

22

Avaya CMS Sun Fire V880/V890 Installation, Maintenance, and Troubleshooting

May 2006

Required tools

You need the following tools to do the installation:

Phillips #2 screwdriver

ESD grounding wrist strap

Antistatic mat

Electrical specifications

Parameter

Value

V880

V890

Input

Nominal voltage range

Maximum current AC RMS

AC operating range

Nominal frequencies

100-240 V AC,

autoranging

15.0 A @100 VAC

90-264 V rms, 47-63Hz

50 Hz or 60 Hz

200-240 V AC,

autoranging

8.0 A @200 VAC

180-264 V rms, 47-63Hz

50 Hz or 60 Hz

Maximum DC power output

2240 W

2509 W

Maximum system AC power

consumption

3000 W

3200 W

Maximum system heat dissipation

10308 BTU/hr

10912 BTU/hr

Volt-ampere rating

1515 VA with 1120 Watt load

(PF=0.99)

2078 VA with 1629 Watt load

(PF=0.98)

Wall plug type

United States

Non-United States

NEMA 5-15P

Power cords must be

obtained locally

NEMA 6-15P

Power cords must be

obtained locally

CPU plug type

IEC 320

IEC 320

Advertising