FP-3000 Specific Parameters

FP-3000 Specific Parameters (In Alphabetical Order)

A_IN_0—A_IN_7

The Expression Block analog input parameters.

A_OUT_0—A_OUT_3

The Expression Block analog output parameters.

A_STATE_0—A_STATE_3

The Expression Block parameters you can use as local variables in an

expression.

ALG_RUN_TIME

The length of time (in milliseconds) the block algorithm takes to run. This
time may be less than the total execution time reported by the block; it does
not include certain overhead external to the block algorithm itself.

BINARY_CL

An interlock input. When in

Discrete_State_1

, the output of the block

is forced closed (

Discrete_State_0

). This interlock input has priority

over all interlock inputs, except

SAFEGUARD_CL

and

SAFEGUARD_OP

. In

the event both

BINARY_OP

and

BINARY_CL

are in discrete state 1, both are

considered to be in

Discrete_State_0

.

BINARY_OP

An interlock input. When in

Discrete_State_1

, the output of the block

is forced open (

Discrete_State_1

). This interlock input has priority

over all interlock inputs, except

SAFEGUARD_CL

and

SAFEGUARD_OP

. In

the event both

BINARY_OP

and

BINARY_CL

are in

Discrete_State_1

,

both are considered to be in

Discrete_State_0

.