Appendix F

Troubleshooting

FieldPoint FP-3000 User Manual

F-6

www.ni.com

The actual mode of a block
switches values.

A block, such as a PID, may switch modes between

Iman

and

Auto

. This means that there is a communications problem

between the PID and the downstream AO block.

Check the schedule. The execution of the PID, AO, and the
communication between them might be scheduled too
close to each other. Space these events further apart and
re-download the configuration.

Check if the stale limit is set correctly for the loop. The
stale limit defines how many old values to accept before
changing

Status

to

Bad

. If the block that is subscribing

the data is executing at twice the rate of a block that is
publishing data, the stale limit must at least be set to 2.

PID block output seems
incorrect.

Make sure that you have set the value of the tuning parameters
like

RATE

,

GAIN

and

RESET

correctly.

Typical values for

GAIN

,

RESET

, and

RATE

are:

GAIN

RESET

RATE

Pressure control

1.2

3.33

0.8

Temperature control

3.0

25.0

10.0

Flow control

0.33

1.11

0.0

Level control

1.9

16.67

2.7

Cannot access or view the
parameters added by National
Instruments.

Make sure that the Device Descriptions are installed in the
correct location. Refer to the section

Import Device

Descriptions

in Chapter 2,

Installation and Configuration

.

Cannot change the values of
certain parameters.

Many configuration parameters of function blocks can be
changed only when the block is in

OOS

mode. Set the mode to

OOS

and then change the configuration parameters.

Table F-3. Generic Software Configuration Problems (Continued)

Problem

Solutions