background image

Chapter 2

Installation and Configuration

FieldPoint FP-3000 User Manual

2-6

www.ni.com

1.

Use a flat-bladed screwdriver to open the rail clip to the unlocked
position, as shown in Figure 2-1.

2.

Snap the panel mount accessory onto the module, as shown in
Figure 2-4.

Figure 2-4. Installing the Network Panel Mount Accessory

3.

Lock the panel mount accessory into place by pushing the rail clip to
the locked position, as shown in Figure 2-1.

4.

Mount the FP-3000 to your panel with the panel mount accessory. The
installation guide that came with the panel mount accessory includes a
guide that you can use to drill pilot holes for mounting the FP-3000.

Connecting Terminal Bases with Panel Mounting

You can install terminal bases directly, without using the panel mount
accessory needed to mount the FP-3000 network module. Follow these
steps to connect terminal bases to a network module using panel mounting.

Caution

To avoid damaging the FP-3000 and the terminal bases, make sure that power is

not applied to the FP-3000 while you install or remove terminal bases.

1.

Drill pilot holes in the panel to mount the terminal bases. A drilling
guide is provided with the network module panel mount accessory.

2.

Attach the terminal base to the FP-3000 by firmly mating the local bus
connectors.

Press