Specifications

This appendix describes the specifications of the FP-3000 network module.

All FieldPoint network modules undergo extensive testing for operating
under rugged environmental conditions that exist in industrial applications.
FieldPoint network modules are designed and tested for immunity and
susceptibility, as well as for emissions.

Network

FP-3000 .................................................. F

O U N D A TIO N

Fieldbus H1

Integrity .................................................. Checksum

Power supply range ................................ 11 to 30 VDC

Power consumption................................ 6 watt + 1.15 *

∑(I/O Module

Consumption)

Maximum terminal bases per bank ........ 9

Maximum number of banks per
Fieldbus link (without repeaters) ........... 32

Environment

Operating temperature............................ –40 to +60 °C

Storage temperature ............................... –55 to +100 °C

Relative humidity ................................... 5% to 90% noncondensing

Compliance

Electrical safety...................................... designed to meet IEC 1010

EMI emissions/immunity ....................... CISPR 11