FP_AO_200_RANGE

Allows the range of a channel on a FieldPoint FP-AO-200 to be adjusted.

FP_AO_210_RANGE

Allows the range of a channel on a FieldPoint FP-AO-210 to be adjusted.

FP_AUTOCONFIGURE

This parameter, present in the resource block, causes the FP-3000 to
automatically configure itself. The FP-3000 detects all the I/O modules
present and instantiates the appropriate I/O function blocks. It creates a
function block for each I/O channel. It tags the function blocks and sets the
contained parameters to appropriate defaults. The resource block must be
set to

OOS

mode before you set the Autoconfigure option. If Autoconfigure

is set on an existing configuration, the FP-3000 deletes all the existing
blocks and linkages before creating new blocks.

FP_CJC_SOURCE

Allows the cold junction compensation to be adjusted on a FP-TC-120
module.

Note

Cold junction compensation is global to the entire module and affects every channel

on the module.

FP_MOD_LIST

This parameter, present in the resource block, lists all the I/O module types
that are currently plugged in.

FP_MOD_STATUS

The status of the FieldPoint I/O module associated with the function block.

Table C-6. Module Status

Status

Description

No Base

There is no terminal base in the specified module position.

Base, But No Module

There is a terminal base in the specified module position, but
no module is installed in the base.

Unconfigured Module

There is a module in the specified position, but the FP-3000
is unable to configure it.