Block_alms_act, Block_reset, Table c-1. block reset options – National Instruments FP-3000 User Manual

Page 104: Cfg_opts, Table c-2. configuration options, Checkback

Advertising
background image

Appendix C

FP-3000 Specific Parameters

FieldPoint FP-3000 User Manual

C-2

www.ni.com

BLOCK_ALMS_ACT

A more detailed explanation of the active block alarms.

BLOCK_RESET

Lets you reset the statistics or the configuration of an individual function
block.

CFG_OPTS

An option in the I/O function blocks to automatically set the scaling or alter
the block behavior. Generally, this option can make configuration easier.

CHECKBACK

A list describing the state of the interlock logic in the CDO block. Use

CHECKBACK

to determine how interlocks are operating.

Table C-1. Block Reset Options

Option

Description

Contained Parameters

Sets all the contained parameters (standard and FP-3000
specific) of the function block to default values. This is useful to
set a specific block to a known state without affecting the
behavior of the other blocks in the FP-3000. The block should
be in

OOS

mode to reset the contained parameters.

Statistics

Resets the various statistics counts associated with the block.

Table C-2. Configuration Options

Option

Description

Automatically Adjust

XD_SCALE

Enabling this option allows the block to automatically
determine its

XD_SCALE

parameter, based on the physical

I/O channel range, which is set by parameters such as

FP_AI_100

range.

Ignore Unconnected Interlock
Inputs

By default, all interlock inputs on the CDO block must be
good, or the block enters fault state. Enabling this option allows
inputs with a status of

Bad::Not_Connected

to be ignored.