Supported fieldpoint modules and channels, Table 4-6. fieldpoint modules, Supported fieldpoint modules and channels -15 – National Instruments FP-3000 User Manual

Page 67

Advertising
background image

Chapter 4

Block Reference

© National Instruments Corporation

4-15

FieldPoint FP-3000 User Manual

Supported FieldPoint Modules and Channels

The FP-3000 supports a wide variety of I/O channels, each with different
types of configuration information. For example, a thermocouple channel
includes parameters for thermocouple type and has ranges for different
temperatures; a current loop channel includes parameters for filter
frequency and has a different group of available ranges to chose from.
Because of these differences in parameters, the FP-3000 has a block
specific to each type of channel it supports. For example, to use a
thermocouple connected to an I/O channel on an FP-TC-120 module, the
FP-3000 provides a FP-TC-120 AI Block. This block is a standard Analog
Input block augmented with parameters specific to the thermocouple
channel on the FP-TC-120.

The FP-3000 does not support all FieldPoint I/O modules. In particular, the
counter module is one module that is often requested, but not supported.
Support for other modules might be added in later firmware revisions.

The following table shows the function block that corresponds to each
supported FieldPoint I/O module.

Table 4-6. FieldPoint Modules

Channel Type

Supported

Module

Block Type

Analog Input

FP-AI-100

Fp Ai 100

FP-AI-110

Fp Ai 110

FP-AI-111

Ap Ai 111

FP-TC-120

Fp Tc 120
Fp Tc 120 C (cold junction
compensation)

FP-RTD-122

Fp Rtd 122

Analog Output

FP-AO-200

Fp Ao 200

FP-AO-210

Fp Ao 210

FP-PWM-520

Fp Pwm 520

Advertising