Figure 2-9. leds on the fp-3000 – National Instruments FP-3000 User Manual

Page 32

Advertising
background image

Chapter 2

Installation and Configuration

FieldPoint FP-3000 User Manual

2-14

www.ni.com

If the self-test suite fails, the FP-3000 does not participate in the network
communication traffic, eliminating potential conflicts with the other banks
in your network.

The FP-3000 has four LED indicators: POWER, NETWORK,
PROCESS, and STATUS. Figure 2-9 shows the LEDs on the FP-3000.

Figure 2-9. LEDs on the FP-3000

The FP-3000 indicates power-on self test failure through the POWER and
STATUS LEDs.

When power is applied, the POWER LED blinks green for approximately
seven seconds during the power on self test. If the self test passes, the
POWER LED turns solid green and the READY LEDs on each
I/O module are lit green. If the self test fails, the POWER LED is lit red
and the module enters an inactive state.

The red STATUS LED is lit when non-volatile memory into memory
buffer fails due to a checksum error. If STATUS is not lit, the FP-3000 has
not detected a failure. The FP-3000 indicates specific error conditions by
flashing STATUS a specific number of times. Table 2-1 describes the
STATUS LED flashing sequences and the corresponding error conditions.

POWER

FF-H1 PORT

PROCESS

STATUS

NETWORK

POWER

FF-H1 PORT

PROCESS

STATUS

NETWORK