Hi_out_d, Init_status, Lambda – National Instruments FP-3000 User Manual
Page 110: Last_block_event

Appendix C
FP-3000 Specific Parameters
FieldPoint FP-3000 User Manual
C-8
www.ni.com
HI_OUT_D
Discrete output indicating state of Hi alarm condition.
INIT_STATUS
The initialization status of the block (used for debugging).
LAMBDA
The frequency response of a PID controller is dominated by the
Proportional, Integral, and Derivative modes in the three frequency regions
shown in the following figure. To limit excessive amplification at high
frequencies, a filter is used to create a “Derivative Limited” region. The
ratio of the derivative term to the filter time constant is defined as lambda.
LAST_BLOCK_EVENT
The last logged event detected by the block. Table C-7 lists descriptions of
the block events. This parameter is useful for debugging configuration
errors because it points to the parameter in error. For example, if an AI
block is in
OOS
mode because
L_TYPE
is not set, the
MGS
would say
Linearization Type Uninitialized
.
Derivative Limited
Derivative
Proportional
Integral
Gain
Phase
Frequency