BIAS (Tuning)

The bias value, in engineering units, used to calculate the function block
output.

BKCAL_HYS (Limiting)

The amount a block’s output value must move off a limit, in percent of
scale, for the limit status to be turned off.

BKCAL_IN (Limiting, Process)

Will be linked to a downstream block’s

BKCAL_OUT

or

SELECT_OUT

parameter. This is used to initialize a control loop through cascade
initialization. Cascade initialization allows smooth transfer for a control
block from manual to automatic mode. To bypass cascade initialization,
this parameter can be left unwired and manually set to a status of

Good,

non-cascade

.

BKCAL_OUT (Process)

A back-calculation value published to the

BKCAL_IN

of an upstream block

in a control loop. The

BKCAL_OUT

parameter has the value of the block’s

current output. Before a cascade loop is initialized, the upstream block can
use this value to smoothly transfer to loop control.

BKCAL_OUT_D (Process)

An output value published to an upstream discrete block. The upstream
block can use this value to smoothly transfer to loop control.

BLOCK_ALM (Alarming, Diagnostic)

An alarm parameter used to report error conditions detected within the
block, such as block Out of Service.

BLOCK_ERR (Diagnostic)

A list of error conditions for hardware and software components associated
with the block.