Table c-7. block events, Last_run_error, Lo_lo_out_d – National Instruments FP-3000 User Manual

Page 111: Lo_out_d, Ltype_domain_index, Nvm_life

Advertising
background image

Appendix C

FP-3000 Specific Parameters

© National Instruments Corporation

C-9

FieldPoint FP-3000 User Manual

LAST_RUN_ERROR

The last run error detected by the block (used for debugging).

LO_LO_OUT_D

Discrete output indicating state of Lo-Lo alarm condition.

LO_OUT_D

Discrete output indicating state of Lo alarm condition.

LTYPE_DOMAIN_INDEX

Virtual field device index of the domain associated with expression in this
AI block.

NVM_LIFE

Remaining useful life of non-volatile memory (NVM).

Table C-7. Block Events

Event

Description

CLASS

The type of event detected.

Configuration Error: An error has been detected in the
configuration of the block.This is usually due to an uninitialized static
parameter. The block updates its

TARGET

mode to

Out of Service

and posts a block alarm.
Operational Warning: The block detected a non-critical event.
The block continues to execute normally.
Operational Error: The block detected a critical event. The block
continues to execute in a higher priority mode.
Internal Error: The firmware detected an internal error.

MSG

A message containing specific details describing the event.

BLOCK_IDX

The index of the block causing the event.

PARAM_IDX

The index of the parameter causing the event.

TARGET_MODE

The

TARGET

mode of the block when the event was detected.

ACTUAL_MODE

The

ACTUAL

mode of the block when the event was detected.

TIME_STAMP

Time when the error was detected.

Advertising