Chapter 3

Example Applications

FieldPoint FP-3000 User Manual

3-6

www.ni.com

3.

To download this schedule to the device, select Configure»Download
Configuration
. The following dialog box appears. This dialog box
enables the configuration to be downloaded. Select the Clear Devices
and Automatic Mode Handling checkboxes, then click on the
Download button. Go through the download process, as described in
the documentation that came with your configurator.

Bring the Block Online

1.

Go to the

MODE_BLK

parameter on the Process tab of the FP-3000

resource block and set the

TARGET

to

Auto

, or click on the Auto button

in the block configuration window.

2.

Go to the

MODE_BLK

parameter on the Process of the block you created

and set the

TARGET

to

Auto

, or click on the Auto button in the block

configuration window.

3.

If the Periodic Updates checkbox is checked, the

MODE_BLK.ACTUAL

parameter should change to

Auto

after a few seconds. Otherwise,

re-read the parameter by clicking on the Read Selected or Read All
button with

MODE_BLK

selected. If it does not go to

Auto

, refer to

Appendix F,

Troubleshooting

, for more information.

Once the block goes to

Auto

, it is fully operational. You can look at the

value of

OUT

on the Process tab and see the pressure reading from the

sensor in inches of water. The pressure reading can be displayed on an
HMI, trended, or used for control (refer to the next example for more
information about using the reading for control).

Close any open block configuration windows before you proceed to the
next example.