Set the input range, Scale the reading, Set the input range -4 scale the reading -4 – National Instruments FP-3000 User Manual

Page 39

Advertising
background image

Chapter 3

Example Applications

FieldPoint FP-3000 User Manual

3-4

www.ni.com

3.

Since the transmitter is wired to the terminals associated with channel
zero on the module, set the

FIELDPOINT_CHANNEL

parameter to

Channel 0

.

Set the Input Range

1.

Click on the

FP_AI_110_RANGE

parameter on the

I/O Config

tab.

2.

Set the parameter to

3.5–21 mA

, since this range most closely

matches the 4–20 mA that you expect from your transmitter.

Scale the Reading

1.

Set the

XD_SCALE

parameter on the Scaling tab, which tells the block

the range of values to expect from the transducer. Enter the following:

XD_SCALE

EU_100

0.020

EU_0

0.004

Units_Index A

Decimal

3