www.ni.com

control. The upstream block signals to the downstream block that cascade
initialization has been bypassed by setting its output to a status of

Good,

Non-cascade

.

Fault State and Mode Shedding

To allow for safe control of a F

O U N D A TIO N

, even in the event the input

sensors or control algorithms fail, F

O U N D A TIO N

Fieldbus provides fault state

and mode shedding. Fault state is used when an output block is in Cascade
mode. Mode shedding is used in Remote or Remote Cascade modes.

Fault State

F

O U N D A TIO N

Fieldbus output function blocks (AO, DO, and CDO) support

a faultstate to deal with the case where the control of the output block has
been lost while the block is in Cascade mode. If the block is in Cascade
mode, and

CAS_IN

has a bad quality for longer than the time specified in

the

FSTATE_TIME

parameter, the block enters faultstate. If the

Faultstate Use Value

option is set in the

IO_OPTS

parameter, the

block uses the value in

FSTATE_VAL

as its output value. If the option is not

set, it holds the value it had at the time the input went bad until the cascade
can be reestablished.

Mode Shedding

For remote modes in which the cascade input is periodically written by a
host application, F

O U N D A TIO N

Fieldbus provides mode shedding to handle

failure of the host application. For the

RCas

mode and

ROut

modes, there

are two timeout parameters in the resource block:

SHED_RCAS

and

SHED_ROUT

. If the block is in a remote mode and the block input being used

(

RCAS_IN

or

ROUT_IN

) is not updated within the timeout period, the block

sheds to a higher priority mode. The action taken by the block when mode
shedding occurs is defined by the

SHED_OPT

parameter. The shed condition

ends when the host writes the remote input parameter. If a normal return
shed option is selected, the block attempts to enter the original remote
mode. If a no return shed option is selected, the target mode is changed at
the time the block sheds mode, and the block does not attempt to enter the
original lower priority mode when the shed condition ends.