Disc_pri (alarming), Dv_hi_alm (alarming), Dv_hi_lim (alarming) – National Instruments FP-3000 User Manual

Page 85: Dv_hi_pri (alarming), Dv_lo_alm (alarming), Dv_lo_lim (alarming), Dv_lo_pri (alarming), Fault_state (faultstate, option), Feature_sel/features (diagnostic, option)

Advertising
background image

Appendix B

Fieldbus Parameters

© National Instruments Corporation

B-7

FieldPoint FP-3000 User Manual

DISC_PRI (Alarming)

Priority of the discrete alarm.

DV_HI_ALM (Alarming)

The current state of the deviation high alarm, along with a time and date
stamp.

DV_HI_LIM (Alarming)

The deviation limit between the PID block setpoint and process value, in
engineering units, beyond which the deviation high alarm is considered
active.

DV_HI_PRI (Alarming)

The priority of the deviation high alarm.

DV_LO_ALM (Alarming)

The current state of the deviation low alarm, along with a time and date
stamp.

DV_LO_LIM (Alarming)

The deviation limit between the PID block setpoint and process value, in
engineering units, beyond which the deviation low alarm is considered
active.

DV_LO_PRI (Alarming)

The priority of the deviation low alarm.

FAULT_STATE (Faultstate, Option)

The current status of the device faultstate. It can be set and cleared with

SET_FSTATE

and

CLR_FSTATE

. If it is set, all output blocks in the device

initiate their own faultstate behavior.

FEATURE_SEL/FEATURES (Diagnostic, Option)

The

FEATURES

parameter lists features supported by the device. Use the

FEATURE_SEL

parameter to manually enable and disable the supported

features listed in the

FEATURES

parameter.

Advertising