DO (Discrete Output)

The DO block writes to a discrete output channel. This block supports
cascade initialization to allow upstream control blocks to determine the
current state of the process before assuming control. It also has a faultstate
behavior that allows the block to react if communications fail between
itself and the upstream block.

CDO (Complex Discrete Output)

The CDO block serves the same purpose as the DO block and adds a
number of parameters to support interlocking at three levels of priority.

LOG (FieldPoint Log Block) (FP-3000 Specific)

The LOG block contains a log of error conditions and events detected by
the device as it operates.

STAT (FieldPoint Statistics Block) (FP-3000 Specific)

The STAT block contains a set of parameters that can be used to examine
how the device is performing. It contains statistics describing the
performance of local function blocks and the network interface.

Table 4-1. CDO Block Interlock Priorities

Input

(Descending Priority)

Notes

Safeguard Close
(

SAFEGUARD_CL

)

Safeguard Close takes priority over any other interlock input.

Safeguard Open
(

SAFEGUARD_OP

)

Safeguard Open takes priority over every other interlock input and is
used to force the block to an open state (

Discrete_State_1

).

Binary Open/Close
(

BINARY_OP/BINARY_CL

)

BINARY_OP

only functions when

ENABLE_OP

has a value of

Discrete_State_1

.

BINARY_CL

only functions when

ENABLE_CL

has a value of

Discrete_State_1

. If both

BINARY_OP

and

BINARY_CL

are set and enabled, neither one takes effect.

Operator Command
(

OP_CMD_CXO

)

OP_CMD_CXO

is a contained bit string parameter that has a bit for

Open and a bit for Close. Open only functions when

ENABLE_OP

has

a value of

Discrete_State_1

. Close only functions when

ENABLE_CL

has a value of

Discrete_State_1

. If both Open and

Close are set and enabled, neither one takes effect.