Appendix B

Fieldbus Parameters

FieldPoint FP-3000 User Manual

B-6

www.ni.com

CYCLE_SEL (Tuning)

Identifies the block execution methods available. Unused in National
Instruments FP-3000.

CYCLE_TYPE (Tuning)

Used to select the block execution method. Unused in National Instruments
FP-3000.

DD_RESOURCE (Diagnostic)

Unused in FieldPoint.

DD_REV (Diagnostic)

The revision of the device description used by the device.

DEV_REV (Diagnostic)

The revision of the device.

DEV_TYPE (Diagnostic)

The manufacturer’s model number for the device.

DISC_ALM (Alarming)

The current state of the discrete alarm, along with a time and date stamp.

DISC_LIM (Alarming)

The discrete input state in which an alarm should be generated.

Use PV for BKCAL_OUT

When set, uses the process variable as the value for

BKCAL_OUT

, instead of the setpoint.

Obey SP Limits if Cas or

RCas

When set, confines the setpoint to values within

SP_HI_LIM

and

SP_LO_LIM

, even when the setpoint comes from another

function block.

No OUT Limits in Man

Unused in FieldPoint.

Table B-2. Control Options (Continued)

Options

Description