Chapter 2

Installation and Configuration

© National Instruments Corporation

2-15

FieldPoint FP-3000 User Manual

The multicolored PROCESS LED is used to indicate the current state of
the processes being controlled by the FP-3000. When a PID function block
on the FP-3000 module is in initialization, the light flashes green. When all
the executing PID blocks on the FP-3000 are in

TARGET

mode, the light

remains lit solid green. Any active alarm of priority greater than eight
results in the light being lit red. For more information on PID blocks, refer
to the section

PID (Proportional–Integral–Derivative)

in Chapter 4,

Block

Reference

.

Table 2-2 describes the NETWORK LED states.

Table 2-1. STATUS LED Flashes and Corresponding Error Conditions

Number of

Flashes

Error Condition

0 (stays lit)

Configuration has changed and has not been stored in
static (non-volatile) memory.

1 green

Parameter storage of nonvolatile and static parameters
has been lost. Re-enter all stored parameters into the
module. You can do this by re-downloading a saved
configuration over the Fieldbus when the Reset switch is
enabled.

2

The FP-3000 detected an error in the terminal bases in
the bank or identified a module in an illegal state. Verify
that the protective cover is on the local bus connector of
the last terminal base and that none of the pins of that
connector are touching or bent. Verify that there are no
more than nine terminal bases in the bank and that no
terminal bases were added to the bank while power was
applied.

Table 2-2. Description of Fieldbus NETWORK LED States

NETWORK LED State

Meaning

Off

Fieldbus port not receiving data.

Flashing green

Fieldbus port is currently the Link Active
Scheduler on the Fieldbus link. The
FP-3000 module is controlling
communications on the Fieldbus.