Figure 2-5. Mounting I/O Module to Terminal Base

Removing I/O Modules

To remove an I/O module, push down on the ejector button at the top of the
terminal base. If the button sticks, you can insert a 1/4" flat-bladed
screwdriver behind the ejector button and twist. This motion unlatches the
I/O module, which can then be lifted off of the terminal base.

Inserting New I/O Modules During Operation

When a new I/O module is inserted, the FP-3000 automatically configures
the I/O module to factory default settings. This configuration is
accomplished without any intervention from the host computer or software.

Replacing I/O Modules During Operation

The host computer can detect missing I/O modules through the block alarm
on the associated function blocks.

When a new I/O module is connected in place of one that was removed, the
FP-3000 first verifies that the replacement I/O module is compatible with
the one that was removed. If the I/O module is either the same as or
compatible with the one removed, the FP-3000 configures the replacement
I/O module with its predecessor’s configuration and output value settings.

1

I/O Module

2

Terminal Base

3

Key

4

Latch

5

Guide Rail

6

Alignment Slot

2

3

4

5

6

1