Momentaryrun mode – Xantrex Technology XW User Manual

Page 111

Advertising
background image

MomentaryRun Mode

975-0307-01-01

C–3

MomentaryRun Mode

For generators with MomentaryRun mode starting types (Type 11):

•

Relay 1 (Run/Stop relay) can be used for two-wire configured
generators.

•

Relay 2 has no unique function in this configuration, but it is easiest
to leave it doing the cranking so that another configuration is not
required for it.

•

Preheat will generally not be used in this configuration.

•

The Preheat will never overlap the Crank Time.

•

The “Delay” refers to the “Preheat to Crank Delay” and may be zero.

•

Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.

Figure C-2 MomentaryRun Mode Timing Diagram