The XW Auto Gen Start Menu

975-0307-01-01

3–7

The Configuration Menu

The Configuration Menu is where specific start-stop parameters are set.
This menu contains the following settings:

QT EN

QT Begin

QT END

Gen Type

Cfg Trigger

Cfg Gen

Multi-unit Config

Restore Defaults

QT En

Full name

Quiet Time Enable

Purpose

“QT En” enables or disables the Quiet Time functionality of the XW Auto
Generator Start. Quiet time refers to a period of time when the generator
should not run.

Dependencies

“QT En” requires the XW Auto Generator Start to be in Automatic mode.
Setting “QT En” to [Enable] requires that parameters be set for the “QT
Begin” and “QT End”.

When to use

Set “QT En” to [Enabled] when there is a period of time when it is not
desired for the generator to run. The XW Auto Generator Start will ignore
all automatic start triggers during the time set in “QT Begin” and “QT
Begin”.

When there are no preferences or restrictions for when the generator
should run, set “QT En” to [

Disabled]

. When [

Disabled]

is selected, the

XW Auto Generator Start will ignore the times set for “QT Begin” and
“QT End”.

Considerations

Quiet Time prevents the automatic starting of the generator regardless of
battery condition.

Value

Description

Enabled/Disabled

Enables or disables the Quiet Time functionality.