Type 12 – Xantrex Technology XW User Manual

Page 42

Advertising
background image

Installation

2–20

975-0307-01-01

Type 12

Type 12 is a three-wire GlowStop configuration recommended for “three-
wire” generators that don’t require a dedicated preheat signal, such as
Onan propane generators. In this configuration, the start signal is applied
for longer because the generator does its own preheat and cranking while
the start signal is applied.

Figure 2-16 Type 12 Connection Diagram

18

17

16

14

13

12

Relay 1

Relay 2

5A fuse

5A fuse

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
STOP

START

XW AGS Harness Wires

Generator Wires

For additional information, see
“Circuit Limitations” on page 2–5.

Table 2-15 Type 12Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

GlowStop

Relay 3 mode

No function

Gen Run signal hold time

4 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

30 s

Crank retry time

40 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3

Advertising