Installing the XW Automatic Generator Start

975-0307-01-01

2–19

Type 11

Type 11 is a two-wire run mode configuration intended for Kohler
generators. It requires only two wires and one relay to control the
generator. Relay 1 closes momentarily once to start the generator, and
closes momentarily again to stop the generator.

Figure 2-15 Type 11 Connection Diagram

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

16

14

13

12

Relay 1

5A fuse

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN

Table 2-14 Type 11 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

MomentaryRun

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

10 s

Crank retry time

15 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3