User settings – Xantrex Technology XW User Manual

Page 82

Advertising
background image

Configuration

3–32

975-0307-01-01

User Settings

Use this table to record any customized XW Auto Generator Start settings
for future reference.

Table 3-3 Generator Configuration Settings, Values, Defaults, and User Settings

Setting

Values

Default

User
Setting

Main Menu Items:

GenMode

ManualOn, ManualOff, Automatic

ManualOff

Mode

Operating/Standby

Operating

Configuration Menu Items:

“QT En”

Enabled, Off

Enabled

“QT Begin”

12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)

9:00PM (12-hour clock)
21:00 (24-hour clock)

“QT End”

12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)

8:00AM (12-hour clock)
8:00 (24-hour clock)

“Gen Type”

Type 1 to Type 13

Type 2

Triggers Menu Items:

“Start DCV 30 sec”

Disabled, 4.0 V–65.0 V

44.0 V

“Start DCV 15 min”

Disabled, 4.0 V–65.0 V

Disabled

“Start DCV 2 hr”

Disabled, 4.0 V–65.0 V

Disabled

“Start DCV 24 hr”

Disabled, 4.0 V–65.0 V

Disabled

“Stop Float”

Enabled, Disabled

Disabled

“Stop Absorb”

Enabled, Disabled

Enabled

“Stop V”

Disabled, 4.0 V–65.0 V

Disabled

“Temp1”

Enabled, Disabled

Disabled

“Temp2”

Enabled, Disabled

Disabled

“Load”

Enabled, Disabled

Disabled

“Start Load”

10.0 A–33.0 A

10.0 A

“Stop Load”

7.0 A–28.0 A

7.0 A

Advertising