Modes of operation – Xantrex Technology XW User Manual

Page 89

Advertising
background image

Modes of Operation

975-0307-01-01

4–5

3. Use the navigation buttons to select the minutes, then press Enter.

If the 24-hour clock is being used, go to step 5.

4. Use the navigation buttons to select AM or PM, then press Enter.

5. Press Exit twice to return to the System Home screen.

To set the end of Quiet Time:

1. On the Auto Gen Start menu, use the navigation buttons to highlight

“QT End”, then press Enter.

2. Use the navigation buttons to select the hour, then press Enter.

3. Use the navigation buttons to select the minute, then press Enter.

If the 24-hour clock is being used, go to step 5.

4. Use the navigation buttons to select AM or PM, then press Enter.

5. Press Exit twice to return to the System screen.

Modes of Operation

The XW Auto Generator Start, like all other Xanbus-enabled devices,
supports two modes, Operating and Standby. The XW Auto Generator
Start mode of operation must be set to Standby before selecting a
Generator Type. Selecting Standby stops the generator (if it is running).

While in Standby, the XW Auto Generator Start

“listens” to and reports

its status to the network. However, it will not start the generator manually
or automatically while in Standby.

If the XW Auto Generator Start

is powered off while in Standby, it will be

in Standby when it is powered on again.

The XW Auto Generator Start can also be put in Standby using the system
mode option under system settings. However, note that selecting Standby
from system settings affects the behavior of the entire XW system.
System mode Standby puts every Xanbus-enabled device in XW Power
System into Standby.

Important:

If XW Auto Generator Start Fault 201 “Unable to stop gen.” is

active, the XW Auto Generator Start cannot be put into Standby. Before Standby
can be established, the generator must be stopped by its external switch and the
fault must be cleared.

Advertising