The XW Auto Gen Start Menu

975-0307-01-01

3–9

QT End

Full name

Quiet Time End

Purpose

“QT End” is a changeable setting that defines the end of quiet time.

This setting also requires a setting for “QT Begin”.

Dependencies

“QT End” functions only if the XW Auto Generator Start is in Automatic
mode. This setting requires “QT En” be set to [Enabled] and also requires
a setting for the “QT Begin” trigger. This setting is triggered by the
setting on the system clock, so ensure the clock on the XW System
Control Panel is set to the correct local time.

Gen Type

Full name

Generator Type

Purpose

“Gen Type” is a changeable setting for selecting the starting requirements
of the generator. The starting requirements determine how the XW Auto
Generator Start must be wired to the generator’s starting system. For more
information, see “Connecting the Generator” on page 2–8 or Appendix B.

Value

Description

12:00AM to 11:59PM
(12-hour clock)
00:00 to 23:59
(24-hour clock)

At the time set for

“QT End”

the XW Auto

Generator Start will be able to automatically start the
generator again. If a start trigger has occurred during
quiet time and is still active, the generator will start
immediately after quiet time ends.

Important:

“Gen Type” can only be changed after the system is put into

Standby. See “Putting the XW Auto Generator Start in Standby Mode” on
page 4–6.

Table 3-1 Generator Type Descriptions and Examples

Option

Description

Mode

For Technical

Details, see...

a

Examples of Generators

b

Type 1

GlowStop

page 2–9

Generac

Type 2

GlowStop with no preheat

page 2–10

Onan Diesel (Default)

Type 3

GlowStop with shutdown bypass

page 2–11

Generac

Type 4

StartStop with Relay 3 prime

page 2–12

Guardian/Generac Gas

Type 5

StartStop with Relay 3 preheat

page 2–13

Guardian/Generac Diesel