Installation

2–16

975-0307-01-01

Type 8

Type 8 will work with both two-wire and three-wire run mode
configurations and is intended for Northern Lights and Fisher Panda
generators. Type 8 is identical to Type 7 except that it provides no preheat
signal before cranking.

Figure 2-11 Type 8 Connection Diagram (two-wire)

Figure 2-12 Type 8 Connection Diagram (three-wire)

Table 2-11 Type 8 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

Run

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3

XW AGS Harness Wires

Generator Wires

16

14

13

12

Relay 1

5A fuse

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
RUN

18

17

16

14

13

12

Relay 1

Relay 2

5A fuse

5A fuse

START

For additional information, see
“Circuit Limitations” on page 2–5.