Xantrex Technology XW User Manual

Page 63

Advertising
background image

The XW Auto Gen Start Menu

975-0307-01-01

3–13

Start DCV 15 min

Full Name

Starting Battery Voltage—15 minutes

Purpose

The “Start DCV 15 min” trigger enables the XW Auto Generator Start to
start the generator whenever the battery voltage reaches or drops below a
pre-set voltage for longer than 15 minutes.

The XW Auto Generator Start will stop the generator when the battery
voltage has risen to the “Stop V”, or when the batteries have been
recharged to the Absorption or Float stage.

Dependencies

The “Start DCV 15 min” trigger requires the XW Auto Generator Start to
be in Automatic mode and needs the “Stop Absorb” or “Stop Float”
trigger be enabled or a parameter to be set for the “Stop V” trigger.

Considerations

If the voltage trigger is set too high, the generator will start more
frequently than is convenient.

If the voltage trigger is set too low, the batteries may be damaged by
repeated cycles of excessive discharge. The generator running time
necessary to charge the batteries may exceed “Max Run Time” and use
too much fuel in the process.

Battery Voltage
Information

Battery voltage can be monitored from the System screen or the inverter/
charger menu.

If “Stop Float” or “Stop Absorb” has been enabled, the generator will stop
when the Float or Absorption stages of the battery charging have begun.

If the “Stop V” is used, the generator will stop when the battery voltage
reaches the parameter set in this trigger, regardless of whether the
batteries are charged.

Values

Default

Disabled, 4.0V to 65.0V

Disabled

Advertising