Type 10 – Xantrex Technology XW User Manual

Page 40

Advertising
background image

Installation

2–18

975-0307-01-01

Type 10

Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.

Figure 2-14 Type 10 Connection Diagram

For additional information, see
“Circuit Limitations” on page 2–5.

18

17

16

14

13

12

Relay 1

Relay 2

5A fuse

5A fuse

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
STOP

START

XW AGS Harness Wires

Generator Wires

Table 2-13 Type 10 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

StartStop

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3