Xantrex Technology XW User Manual

Page 83

Advertising
background image

User Settings

975-0307-01-01

3–33

Generator Menu Items:

“Starter Cool Down”

1s to 250s (increments of 1s)

60s

“Gen Cool Down”

0s to 90 s (increments of 1s)

30s

“Max Run Time”

0hours–24 hours

8hours

“Exercise Per”

0days (Off)–250days

21days

“Exercise Dur”

1min–250min

30min

“Exercise Time”

12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)

9:00AM (12-hour clock)
9:00 (24-hour clock)

“Relay3”

Preheat, WrmupCoolDn, Preheat
SDByp, NotUsed

NotUsed

“Gen Run Hold
Time”

0.5s to 20s (increments of 1s)

0.5s

“Crank Delay”

0s to 60s (increments of 1s)

0s

“Crank Time”

0s to 250s (increments of 1s)

30s

“Crank Retry Time”

0s to 250s (increments of 1s)

40s

“Preheat Time”

0s to 250s (increments of 1s)

0s

“Gen Start Tries”

1 to 10

3

Multi-Unit Configuration:

“Dev Name”

1-15 characters

XW AGS

“Dev Number”

00 to 31

00

Connections:

“DC Conn”

None, HouseBatt1 to 6,
StartBatt1 to 6

HouseBatt1

“AC In”

None, Grid1to 10, Gen1 to 10

Grid1

“AC Out”

None, ACLoad1 to 10

ACLoad1

“Generator”

Gen1 to 10

Gen1

Table 3-3 Generator Configuration Settings, Values, Defaults, and User Settings

Setting

Values

Default

User
Setting

Advertising