Installing the XW Automatic Generator Start

975-0307-01-01

2–7

Table 2-3 Contact Numbers and Functions

Wire
Number

Function

Wiring Harness
Wire Color

1

Thermostat 1 input

Yellow

2

Thermostat 1 return

Gray

3

Thermostat 2 input

Orange

4

Thermostat 2 return

Gray

5

External shutdown input

White/Black

6

External shutdown return

Gray

7

External manual on input

White/Green

8

External manual off input

White/Red

9

External ON/OFF LED Indicator output

White/Blue

10

Constant 12/24 V B+ (battery positive) for
External ON/OFF/LED Indicator

Red

11

External ON/OFF/LED Indicator return
(connected internally to wire number 13)

Black

12

Generator run signal (switched B+) sense input

Violet

13

Generator run signal (switched B+) sense return
(generator battery negative)

Black

14

Relay 1 (Generator run/stop) Normally open
contact

Blue

15

Relay 1 (Generator run/stop) Normally closed
contact

White/Violet

16

Relay 1 (Generator run/stop) Common contact

Gray

17

Relay 2 (Generator start) Normally open contact

White

18

Relay 2 (Generator start) Common contact

Gray

19

Relay 3 (Preheat/cooldown) Normally open
contact

Brown

20

Relay 3 (Preheat/cooldown) Common contact

Gray

Advertising