Installing the XW Automatic Generator Start

975-0307-01-01

2–17

Type 9

Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3. This configuration is intended for Westerbeke
generators.

Figure 2-13 Type 9 Connection Diagram

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

18

17

16

14

13

12

20

19

FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +

Relay 1

Relay 3

Relay 2

5A fuse

5A fuse

5A fuse

GENERATOR RUN SIGNAL

STOP

START

GENERATOR BATTERY NEGATIVE (–)

Table 2-12 Type 9 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

StartStop

Relay 3 mode

Shutdown Bypass

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Shutdown bypass time

5 s

Start tries

3