Starting and Stopping the Generator

975-0307-01-01

4–3

Starting and Stopping the Generator

Use the XW Auto Generator Start to start or stop the generator manually
using the XW System Control Panel or automatically in response to an
electrical system condition.

To set the XW Auto Generator Start to start and stop the generator
automatically:

1. On the XW Auto Generator Start menu, highlight GenMode and press

Enter.

2. Use the navigation button to select [Automatic].

3. Press Enter.

To start the generator manually:

1. On the XW Auto Generator Start menu, highlight GenMode and press

Enter.

2. Use the navigation button to select [ManualOn].

3. Press Enter.

To stop the generator manually:

1. On the XW Auto Generator Start menu, highlight GenMode and press

Enter.

2. Use the navigation button to select [ManualOff].

3. Press Enter.

Important:

To avoid XW Auto Generator Start faults, try not to

combine automatic and external manual starts and stops.

When the generator has been started automatically, allow it to stop
automatically unless a situation occurs that requires the generator to be
stopped urgently.

Likewise, if the generator has been started manually, ensure that it is
stopped manually. Only the “Max Run Time” setting can automatically
stop the generator after it has been started manually.

Figure 4-2 Starting and Stopping the Generator

XW System Home Screen

Select Device Menu

Auto Gen Start Menu