Type 4 – Xantrex Technology XW User Manual

Page 34

Advertising
background image

Installation

2–12

975-0307-01-01

Type 4

Type 4 is a three-wire StartStop configuration that uses relay 3 to provide
the preheat signal for Generac’s Guardian Gas generators.

Figure 2-6 Type 4 Connection Diagram

XW AGS Harness Wires

Generator Wires

18

17

16

14

13

12

20

19

FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +

Relay 1

Relay 3

Relay 2

5A fuse

5A fuse

5A fuse

GENERATOR RUN SIGNAL

STOP/PREHEAT

START

GENERATOR BATTERY NEGATIVE (–)

For additional information, see
“Circuit Limitations” on page 2–5.

Table 2-7 Type 4 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

StartStop

Relay 3 mode

Preheat

Gen Run signal hold time

10 s

Preheat time

60 s

Preheat to crank delay

5 s

Crank time

15 s

Crank retry time

15 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3