background image

Installing the XW Automatic Generator Start

975-0307-01-01

2–11

Type 3

Type 3 is a three-wire GlowStop with shutdown bypass configuration.
The configuration shown in Figure 2-5 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown
functionality during cranking. Generators with this functionality often
have a manual means of disabling it during cranking.

Figure 2-5 Type 3 Connection Diagram

Table 2-6 Type 3 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

GlowStop/Shutdown bypass

Relay 3 mode

Preheat/Shutdown bypass

Gen Run signal hold time

0.5 s

Preheat time

20 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Shutdown bypass time

10 s

Start tries

3

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

14

13

12

18

17

16

Relay 1

Relay 2

5A fuse

5A fuse

GENERATOR RUN SIGNAL

START

PREHEAT
STOP
BYPASS SHUTDOWN

GENERATOR BATTERY NEGATIVE (–)