Type 1 – Xantrex Technology XW User Manual

Page 31

Advertising
background image

Installing the XW Automatic Generator Start

975-0307-01-01

2–9

Type 1

Type 1 is a three-wire GlowStop configuration recommended for “three-
wire” generators with glow plugs that need to be operated before a start is
attempted.

Figure 2-3 Type 1 Connection Diagram

18

17

16

14

13

12

Relay 1

Relay 2

5A fuse

5A fuse

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
PREHEAT

START

XW AGS Harness Wires

Generator Wires

For additional information, see
“Circuit Limitations” on page 2–5.

Table 2-4 Type 1 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

GlowStop

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

20 s

Preheat to crank delay

1 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3