Installing the XW Automatic Generator Start

975-0307-01-01

2–21

Type 13

Type 13 is a three-wire PulseStop configuration that uses relay 3 to
provide the preheat signal for PowerTech’s Diesel generators. With this
generator type, there will be a delay between the generator turning off and
the XW Auto Generator Start recognizing that the generator is off.

Figure 2-17 Type 13 Connection Diagram

Table 2-16 Type 13 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

PulseStop

Relay 3 mode

Preheat

Gen Run signal hold time

5 s

Preheat time

15 s

Preheat to crank delay

2 s

Crank time

15 s

Crank retry time

15 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

18

17

16

14

13

12

20

19

FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +

Relay 1

Relay 3

Relay 2

5A fuse

5A fuse

5A fuse

GENERATOR RUN SIGNAL

STOP/PREHEAT

START

GENERATOR BATTERY NEGATIVE (–)