Installation

2–14

975-0307-01-01

Type 6

Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact. This generator type is intended for Yamaha generators.

Figure 2-8 Type 6 Connection Diagram

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

18

17

16

15

13

12

14

Relay 2

Relay 1

5A fuse

5A fuse

5A fuse

GENERATOR RUN SIGNAL
GENERATOR BATTERY NEGATIVE (–)
PREHEAT
STOP

START

Table 2-9 Type 6 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

GlowStop

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

10 s

Preheat to crank delay

1 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3