Relay Timing

C–6

975-0307-01-01

The XW Auto Generator Start will make three attempts to stop the
generator. If the generator has still not stopped at the end of the third
attempt, the appropriate Fault will be generated.

Each stop attempt will consist of engaging the stop relay for 5 seconds
and then waiting 20 seconds before checking the state of the Gen Run
Signal to see if the stop attempt was successful.

Figure C-5 PulseStop Mode Timing Diagram

Figure C-6 PulseStop Mode Relay 1 Behavior